Areas of application - Hot smoke extraction, up to a maximum of 400°C/2 h, in accordance with EN12101-3 (F400)
- Cold smoke extraction, with maximum of 120°C in continuous operation
- Process air, with a maximum of 120°C in continuous operation
Technical details - Cage motors outside the air flow
- Minimum media temperature: -25°C
- Maximum media temperature: +400°C/2 h, in accordance with EN12101-3 (F400)
- Maximum dust content: 5 mg/m³
Models available - Available only as tiltable version, to ensure simple maintenance work: RJVH
- Fan switch for simple ON and OFF switching, included in scope of delivery
Product description - Air-flow optimized with non-swirl-oriented, vertical air outlets
- Automatic cover flaps included in scope of delivery
Motor versions available - 400V, 1-speed motors
- 400V, 2-speed Dahlander motors
Control packages - 2-step switch, especially for the control of Dahlander multispeed motors
Extensive accessories available, including - Base with and without intake-side noise suppression
- Protective grating against hand or finger contact, intake-flow nozzle, spacers, sailcloth adapters, and much more
|