Smoke extraction:  

GEA RoofJETT model RVJH






Areas of application

  • Hot smoke extraction, up to a maximum of 400°C/2 h, in accordance with EN12101-3 (F400)
  • Cold smoke extraction, with maximum of 120°C in continuous operation
  • Process air, with a maximum of 120°C in continuous operation

Technical details

  • Cage motors outside the air flow
  • Minimum media temperature:  -25°C
  • Maximum media temperature:  +400°C/2 h, in accordance with EN12101-3 (F400)
  • Maximum dust content:  5 mg/m³

Models available

  • Available only as tiltable version, to ensure simple maintenance work:  RJVH
  • Fan switch for simple ON and OFF switching, included in scope of delivery

Product description

  • Air-flow optimized with non-swirl-oriented, vertical air outlets
  • Automatic cover flaps included in scope of delivery

Motor versions available

  • 400V, 1-speed motors
  • 400V, 2-speed Dahlander motors

Control packages

  • 2-step switch, especially for the control of Dahlander multispeed motors

Extensive accessories available, including

  • Base with and without intake-side noise suppression
  • Protective grating against hand or finger contact, intake-flow nozzle, spacers, sailcloth adapters, and much more


Smoke extraction