Exhaust air extraction from explosion-endangered areas (Class EEx areas), up to +40°C: GEA RoofJETT models RJVX / RJVY
|
|
|
|
|
|
|

Areas of application - Warehouse areas with stored substances giving rise to potentially explosive atmospheres
- Production shop floors with potentially explosive atmospheres
Technical details - Cage motors outside the air flow
- Minimum media temperature: -25°C
- Maximum media temperature: +40°C
- Maximum dust content: 5 mg/m³
- Version RJVX for Class EEx e T3 (= 200°C)
- Version RJVY for Class EEx d T4 (= 135°C)
Models available - Tiltable version to ensure simple maintenance work: RJVX, RJVY
- Fan switch for simple ON and OFF switching is included in the scope of delivery
Product description - Air-flow optimized with non-swirl-oriented, vertical air outlets
- Automatic cover flaps included in scope of delivery
Motorvarianten Control packages - Stepping switch for installation outside EEx potentially explosive atmospheres
Extensive accessories available, including - Base with and without intake-side noise suppression
- Protective grating against hand or finger contact, intake-flow nozzle, spacers, sailcloth adapters, and much more
|
|
|
|
|
|
|